避雷器使用场所
|
型号
|
系统标称电压有效值
kV
|
避雷器额定电压有效值
kV
|
避雷器持续运行电压有效值
kV
|
直流1mA参考电压
≥
kV
|
标称放电电流5kA
|
通流容量
|
|||
陡坡冲击电流残压
峰值
≤
kV
|
雷电冲击电流残压
峰值
≤
kV
|
操作冲击电流残压
峰值
≤
kV
|
2ms方波
冲击电流
≥
A
|
4/10us大
电流冲击
≥
kA
|
||||||
低压型
|
HY1.5W-0.28/1.3
|
0.22
|
0.28
|
0.24
|
0.60
|
-
|
1.3
|
-
|
50
|
10
|
HY1.5W-0.5/2.6
|
0.38
|
0.50
|
0.42
|
1.20
|
-
|
2.6
|
-
|
50
|
10
|
|
配电型
|
HY5WS-5/15
|
3
|
5
|
4.0
|
8.0
|
19.6
|
15.0
|
14.5
|
100
|
65
|
HY5WS-10/30
|
6
|
10
|
8.0
|
15.0
|
34.5
|
30.0
|
25.5
|
100
|
65
|
|
HY5WS-17/50
|
10
|
17
|
13.6
|
25.0
|
57.5
|
50.0
|
42.5
|
100
|
65
|
|
电
站
型
|
HY5WZ-5/13.5
|
3
|
5
|
4.0
|
7.5
|
15.5
|
13.5
|
11.5
|
200
|
65
|
HY5WZ-10/27
|
6
|
10
|
8.0
|
14.4
|
31.0
|
27.0
|
23.0
|
200
|
65
|
|
HY5WZ2-17/45G
|
10
|
17
|
13.6
|
24.0
|
51.8
|
45.0
|
38.3
|
200
|
65
|
|
HY5WZ-51/134
|
35
|
51
|
40.8
|
73.0
|
154.0
|
134.0
|
114.0
|
400
|
65
|
|
发
电
机
型
|
HY5WD-4/9.5
|
3.15*
|
4
|
3.2
|
5.7
|
10.7
|
9.5
|
7.6
|
400
|
65
|
HY5WD-8/18.7
|
6.3*
|
8
|
6.3
|
11.3
|
21.0
|
18.7
|
15.0
|
400
|
65
|
|
HY5WD-13.5/31
|
10.5*
|
13.5
|
10.5
|
18.6
|
34.7
|
31.0
|
25.0
|
400
|
65
|
|
HY5WD-17.5/40
|
13.8*
|
17.5
|
13.8
|
24.4
|
44.8
|
40.0
|
32.0
|
400
|
65
|
|
电
动
机
型
|
HY2.5WD-4/9.5
|
3.15*
|
4
|
3.2
|
5.7
|
10.7
|
9.5
|
7.6
|
200
|
65
|
HY2.5WD-8/18.7
|
6.3*
|
8
|
6.3
|
11.3
|
21.0
|
18.7
|
15.0
|
200
|
65
|
|
HY2.5WD-13.5/31
|
10.5*
|
13.5
|
10.5
|
18.6
|
34.7
|
31.0
|
25.0
|
200
|
65
|
|
中性点型
|
HY1.5WD-2.4/6
|
3.15*
|
2.4
|
1.9
|
3.4
|
-
|
6.0
|
5.0
|
200
|
65
|
HY1.5WD-4.8/12
|
6.3*
|
4.8
|
3.8
|
6.8
|
-
|
12.0
|
1.0
|
200
|
65
|
|
HY1.5WD-8/19
|
10.5*
|
8
|
6.4
|
11.4
|
-
|
19.0
|
15.9
|
200
|
65
|
|
电
容
器型
|
HY5WR-10/27
|
6
|
10
|
8
|
14.4
|
-
|
27.0
|
21.0
|
400/600
|
65
|
HY5WR-17/46
|
10
|
17
|
13.6
|
24.0
|
-
|
46.0
|
35.0
|
400/600
|
65
|
|
HY5WR-51/134
|
35
|
51
|
40.8
|
73.0
|
-
|
134.0
|
105.0
|
400/600
|
65
|
|
注:“*”表示电机额定电压有效值。
|